GT SYSTEM 600 AUTOMATIC FIRE DOOR
USING THE GYRO SWING
SPRING CLOSE OPERATOR
SUGGESTED ARCHITECTURAL SPECIFICATIONS
SECTION 8
AUTOMATIC ENTRANCE SYSTEMS
PART 1-GENERAL
1.01 DESCRIPTION
A.
Furnish and install automatic entrance equipment as indicated on
drawings and as specified.
B.
Related work specified elsewhere.
1. Electrical
Supply: Section _______
2. Floor
Preparation: Section _______
1.02 QUALITY ASSURANCE
A.
Manufacturer's Qualifications:
Products specified shall be represented by a
factory authorized and trained distributor. Distributor shall maintain a parts
inventory and trained personnel capable of providing service.
B.
Requirements of Regulatory Agencies:
1.
Underwriters Laboratory, Inc. (UL): Automatic entrance and/or exit
doors shall be a UL listed system in guide FDDR and/or guide FUXV.
2.
National Fire Protection Association (NFPA); Automatic Fire Door
Assemblies shall be approved for use with UL listed door frames and latching
devices as designated by NFPA 101 and NFPA 80.
C.
All automatic equipment to comply with ANSI A156.10.
D.
Gyro Tech equipment as manufactured by NABCO ENTRANCES, INC. has been
specified and shall be quoted as the base bid. Other systems may be quoted
along with information specifically detailing the differences from the
following specification.
1.03 SUBMITTALS
A.
Shop drawings showing complete elevations, details and method of
anchorage to location; installation of hardware; size, shape, joints and
connections; and details of joining with other construction.
B.
Templates and diagrams and/or shop drawings as needed shall be
furnished to fabricators and installers of related work for coordination of
operators with doors, frames, hardware, concrete work and other work.
C. A copy of appropriate
manual shall be provided to owner's engineer upon completion of installation.
1.04 WARRANTY
A.
Warranty of power operators, controls and labor provided by automatic
door equipment installer against defects in material and workmanship at no
cost to owner, for a period of one year from date of substantial completion.
Provide warranty to owner after completion of installation.
1.05 COMPLIANCE
A.
A completed American Association of Automatic Door Manufacturers (AAADM)
form shall be submitted as proof of compliance with ANSI 156.10 Standard for
power operated pedestrian doors. Door(s) shall be inspected and form shall be
signed by an AAADM certified inspector prior to placing door(s) in operation.
PART 2-PRODUCTS
2.01 APPROVED MANUFACTURER
A.
Automatic entrance equipment and controls shall be distributed by:
Ontario Door Controls
1350 Matheson Boulevard East
Unit 16, Mississauga
Ontario, Canada.
Phone: (905) 238 9222
Fax
: (905) 238 9279
e-mail:
products@automaticdoorsystems.com
Website: http://www.automaticdoorsystems.com
2.02 AUTOMATIC SWING DOOR SYSTEM
A.
GYRO TECH System 600 (surface applied) automatic swing door system for
automating fire doors as indicated on door schedule and details.
B.
Mode of Operation: Spring-Close. Gyro-Swing operator shall open door by
energizing motor and shall stop door by electrically reducing voltage and
stalling motor against mechanical stop. Door shall close slowly by means of
spring energy, and closing force shall be controlled by gear system and motor
being used as dynamic brake without power. System shall also operate as a
manual door in event of power failure. Manual operation shall require less
than 15 lbs. force applied to door stile. Opening and closing speeds shall be
adjustable. Door operation shall not require any fluids or gases under
pressure to be used in opening and closing of door.
C.
Components:
1. Operator Housing
2. Gyro-Swing Power Operator
3. Electronic Control
4. Soft Start
5. Connecting Hardware
6. Accessory Package (single or
double doors)
1a)
Operator Housing: GYRO TECH Housing shall be 5-1/2" (139.7 mm)
wide by 5" (127.0 mm) high aluminum extrusions with finished end caps and
shall be prepared for mounting to new or existing door frames. All structural
sections shall have a minimum thickness of 0.146" (3.7mm) and shall be
fabricated of 6063-T5 aluminum alloy.
1b)
Finish: Aluminum shall have a standard finish of AA-M12-C22-A41 (204
R1) or AA-M12-C22-A42 (dark bronze). Black and special finishes available upon
request.
2)
Gyro-Swing Power Operator: Completely assembled and sealed unit which
shall include helical gear-driven transmission, overriding clutch (to provide
easy manual operation. spring-close). mechanical spring and bearings, all
located in cast aluminum housing and filled with special lubricant for extreme
temperature conditions. Attached to transmission system shall be a DC
shunt-wound permanent magnet motor with sealed ball bearings. Motor shall
operate from 115-volt supply and require less than 5 amps at full power stall.
Complete unit shall be resilient mounted with provisions for easy replacement,
without removing door from pivots or frame.
3)
Electrical Control: Self-contained unit including necessary
transformer, relays, rectifiers, and other electronic components for proper
operation and switching of Gyro-Swing power operator. Relays shall be plug-in
type for individual replacement. All connecting harnesses shall have
interlocking plugs. Controls shall also include time delay for normal cycle.
Control shall include safe-swing circuit as optional switching which
automatically limits power and slows door when approached from passive side.
4)
Soft Start: Energy limiter shall be a modular electronic current
control for the purpose of controlling torque to limit stress on entire
entrance package.
5)
Connecting Hardware: Connect conversion unit (CU) drive arm to inswing
door with a urethane covered roller, which shall ride in a track fabricated of
6061-T6 aluminum alloy attached to the top door rail where required for
pull-type operation. Outswing doors shall be connected to operator by a
two-piece drive arm with self-aligning rod ends and connecting door bracket
for push-type operation.
6)
Accessory Package: Provide one GYRO TECH UL listed fire door accessory
package for each door consisting of:
6a) Latch
Mechanism (retractor) (double door only)
6b) Power
Reset Box (double door only)
6c) Power
Box (single door only)
6d) Caution
Labels
NOTE: Double Doors UL listed only with Von Duprin 8827-F Surface
applied, UL Listed Exit hardware. Single Door UL Listed only with Von Duprin
3041 Electric Strike and Von Duprin 8875-F Mortise Lock
2.03 ACTIVATING DEVICES
A.
Wall Switches: 6" (152.4 mm) diameter stainless steel, surface or
plain, as manufactured by NABCO ENTRANCES, INC.
B.
Carpet Activators: Of sizes and colors as required shall be
manufactured by NABCO ENTRANCES, INC.
C.
Optional activators are available - See Product Catalog.
PART 3-EXECUTION
3.01 INSTALLATION
A.
Automatic door equipment shall be installed by factory-trained
installers in compliance with manufacturer's recommendations and approved shop
drawings.
3.02 CLEANING AND PROTECTION
A.
After installation, clean framing members as recommended by
manufacturer. Aluminum surfaces in contact with masonry, concrete, and steel
shall be protected by use of neoprene gaskets where indicated, or a coat of
bituminous paint to prevent galvanic or corrosive action. Advise general
contractor to protect unit from damage during subsequent construction
activities.
* COVER NOTE TO SPECIFICATION
WRITER
Indicate under appropriate Section
the following work by others.
ELECTRICAL INSTALLER shall furnish and install all
conduit and electrical wiring for activating devices and door operators. A
minimum of 5 amperes, 115-volt, A/C, 1-phase circuit shall be furnished of
each door operator, terminate and connect to operator control panel in
operator housing.
CONCRETE INSTALLER shall prepare floor at location
of automatic entrance system to accommodate the surface or recessed electric
switch mats as indicated on drawings.